Study of the risk of COVID-19 infection in a retirement home

     Objective: Confirm that the EHPAD ventilation system will maintain acceptable levels of SARS-COV-2 concentration in the east wing, a future service dedicated to residents with COVID-19.

covid19 ehpad

Context

Scenarios examined

Building

  • Retirement home
  • East wing of the building
  • Bedroom : 18,2m2
  • Bathroom: 4,4m2
  • Corridor adjoining bedroom : 47,2m2

Ventilation system

  • Double flow AHU
  • Air renewal set at 3 ACPH

Les scénarios

Scenario 1

CTA air renewal of 3.0 vol/h

Scenario 2

Air renewal provided by the CTA of 3.0 vol/h + Purifier with a nominal flow rate of 455m3/h

Scenario 3

CTA air renewal of 6.0 vol/h

Results

This study quantified the impact of two preventive measures on the risk of COVID-19 infection : the installation of an ai purifier in the infected resident’s bedroom and incrasing the air renewal rate to 6 ACPH.

In the case of a room adjacent to the patient’s bedroom: 

– The air purifier in the patient’s room reduces infectious risk by 66% (scenario 2).
– Increasing air renewal in the patient’s room reduces infectious risk by 55% (scenario 3).

In the corridor: 
– The air purifier in the patient’s room reduces infectious risk by 67% (scenario 2).
– At a 6 vol/h air renewal rate (scenario 3), the infectious risk is reduced by just 33%

Our recommandations and conclusions

1

The most effective measure to limit the propagation of the virus in other areas seems to be the use of a purifier in the patient’s room.

2

COVID-19 infected patients’ rooms should be located primarily to the southwest wing, in order to limit particulate matters transportation.

3

Balancing blow and return flows is essential to limite virus spreading risk in bedrooms and corridors.